The two-part test sets PGK HB generate variable AC test voltages of mains frequency or DC voltages of positive or negative polarity.
The operating unit in 19“ design has a voltage and current display, safety control elements according to VDE 0104 and a variable transformer for voltage adjustment.
The high voltage unit contains an oil insulated high voltage transformer and, depending on the desired operation mode, a rectifier rod or a resistor rod. The polarity of the DC test voltage can be changed by reversing the rectifier in the high voltage unit.
Features:
absolutely maintenance-free design
stepless adjustable output voltage
safety control according to VDE 0104
short-circuit protected by internal current limitation
voltage indication: 2 range analogue meter, ratio 1:3
current measurement: 3 range analogue meter, decadic thermal overcurrent switch-off
Technical data
| PGK 70 / 2,5 HB | |
Mains supply | 220 - 240 V | |
| 110 - 120 V with external | |
| autotransformer | |
Mains frequency | 45 Hz up to 60 Hz | |
Power consumption |
| 3200 VA |
Power consumption short-circuit |
| 6500 VA |
Nominal output voltage AC rms / DC | 55 kV / 70 kV | |
Output current cont. AC rms / DC | 50 mA / 20 mA | |
Short-circuit current AC rms / DC | 117 mA / 84 mA | |
Relative humidity | not condensing | |
Ambient temperature | working: | 0 ... + 45 ° C |
| storage: | - 20 ... + 60 ° C |
Precision of the kV-meter |
| 2,5 % |
Precision of the mA-meter |
| 2,5 % |
Dimension control unit housing (W x H x D) | 502 x 241 x 290 mm | |
Dimension High Voltage part (height / diameter) | 1130 mm / 455 mm | |
Weight control unit |
| 22 kg |
Weight High Voltage unit |
| 93 kg |
下一篇:继电保护测试仪配件,DCC