作者:凯迪正大股份来源:金沙2004cmapp下载主页日期:2015-09-12 09:29:00阅读:
The two -part test sets PGK HB generate variable AC test voltages of mains frequency or DC voltages of positive or negative polarity.
The operating unit in 19“ design has a voltage and current display, safety control elements according to VDE 0104 and a variable transformer for voltage adjustment.
The high voltage unit contains an oil insulated high voltage transformer and, depending on the desired operation mode, a rectifier rod or a resistor rod. The polarity of the DC test voltage can be changed by reversing the rectifier in the high voltage unit.
Features:
·absolutely maintenance-free design
· stepless adjustable output voltage
· safety control according to VDE 0104
· short-circuit protected by internal current limitation
· voltage indication: 2 range analogue meter, ratio 1:3
· current measurement: 3 range analogue meter, decadic
· thermal overcurrent switch-off
Technical data
| PGK 150 / 5 HB | |
Mains supply | 220 - 240 V | |
| 110 - 120 V with external | |
| autotransformer | |
Mains frequency | 45 Hz up to 60 Hz | |
Power consumption |
| 5750 VA |
Power consumption short-circuit | 11700 VA | |
Nominal output voltage AC rms / DC | 110 kV / 150 kV | |
Output current cont. AC rms / DC | 50 mA / 18 mA | |
Short-circuit current AC rms / DC | 108 mA / 77 mA | |
Relative humidity | not condensing | |
Ambient temperature | working: | 0 ... + 45 ° C |
| storage: | - 20 ... + 60 ° C |
Precision of the kV-meter |
| 2,5 % |
Precision of the mA-meter |
| 2,5 % |
Dimensions control unit housing (W x H x D) | 502 x 580 x 480 mm | |
Dimensions High Voltage part (height / diameter) | 1530 mm / 640 mm | |
Weight control unit |
| 51 kg |
Weight High Voltage unit |
| 180 kg |